SF6 gas comprehensive analyzer
Apps
Analysis of gas quality in SF6 aeration equipment

Features
modular instrumentation that determines four SF6 gas parameters (purity, humidity, SO2 concentration, and HF concentration)
Integrated data processing and storage capabilities
Verification of measurement data in accordance with CIGRE, IEC or customer specified limits
Test speed is fast, just about 5… 7 minutes
Easy to use

Description
GA10 analyzer is an innovative and cost-effective solution for determining the quality of SF6 gas.
Configurable separately
GA10 includes a basic instrument with display and an integrated electronic data acquisition and processing device, with a fully modular design, allowing users to expand the basic instrument using the sensor box. In addition, the sensor box used by the user can be sent to the manufacturer for separate verification.
As long as the complete instrument is equipped, the analyzer can measure the purity, humidity, SO2 concentration or HF concentration of SF6 gas. In addition, the GA10 analyzer can also be used to determine the pressure dew point of SF6 gas by measuring the pressure and humidity of the test gas. By comprehensively measuring all of the above measurement parameters, the measurement time and the amount of gas required for measurement can be minimized.
Measuring instruments come standard with accessories and shipping boxes.
Easy to use
This model is equipped with a rotary switch and clear menu navigation, making it easy and easy for users to operate.
After the measurement is started, the sensor measurements are automatically compared to the limits of CIGRE B3.01.01, IEC or customer-specified standards.
After the measurement is complete, two status indicators (red and green) indicate whether the composition of the test gas meets the set limits.
The analyzer's internal measurement store can store at least 150 data records. Users can export and store data to a computer using the SF6-Reviewer software (included in the scope of delivery).
Environmental
The GA45 gas recovery bag can be connected to the outlet of the GA10 analyzer to collect the measurement gas.

2019/07/25 11:09:08

706