×
SF6 gas density switch (high pressure)
Apps
Gas density monitoring of closed SF6 tanks
Outdoor use
for high voltage switchgear

Features
Density switch with reference chamber and gas compensation function
There is a micro switch in the reference gas chamber; it is not affected by atmospheric pressure changes and altitude; no need to re-check

Description
Scope of work
Allow fill pressure:
1.1 MPa (absolute) / 20 ° C
Recommended gas chamber maximum pressure:
0.75 MPa (absolute) / 20 ° C
Recommended gas chamber minimum pressure:
0.4 MPa (absolute) / 20 ° C
Allowable temperature range
Ambient temperature: -40 … +80 ° C (gas phase)
Storage temperature: -40 … +80 °C
Alarm contacts / contact rating
Up to 4 microswitches can be used for on or off operation, switching point (not adjustable) has been fixed according to customer requirements
Contact Rating: 5 A / 250 V AC, 50 Hz
Switch strokes
Maximum switching point travel: 0.16 MPa
Minimum switching point travel: 0.01 MPa
Switch hysteresis: usually 0.01 MPa, switching point settings meet product specifications
Reference accuracy of reference electrical contacts
20 ​​°C: 6 kPa
-20 ... +60 °C: 8 kPa
High Pressure Test
2 kV, 50 Hz, 1 second (for the case wiring)
Electrical connections
Cable box with M20 x 1.5 cable gland
The wire cross-sectional area is up to 2.5 mm2

2019/07/25 14:02:26

795