Welcome to Nordic Energy!

TEL:0510-85135958
Fire Equipment

Test and drain valve


       In a sprinkler system, it is used to test the system and expel unnecessary liquid from the system.
        Advantages: The valve body has a built-in sight glass, and a single valve is enough to discharge water from the pipeline.
        When selecting test and drain valves, pay attention to the pipe diameter. At the same time, the diameter must be the same as the orifice diameter of the sprinkler.
 
Table 8.16.2.4.2. – NFPA13
Pipe diameter (inches) Test and drain valve diameter (inches)
≤ 2”  ≥ ¾”
 2 ½”, 3”, 3 ½”  ≥ 1 ¼”
≥ 4” 2”
 
Connection Type
        Thread or groove
 
Work pressure
        300 psi
 
diameter
        1” – 2”
 
Material characteristics
        Body: brass
        Valve ball: brass
 
Application range
        Sprinkler system
 
Certification
        -UL certification
        -Ulc certification
        -FM certification
 
Product manual
        Click here to download Test and Drain Valve Manual
        Download Brochure (PDF)

CONTACT US

  • TEl:0510-85135958
  • FAX:0510-85131358
  • E-MAIL:nordictech@nordictech.com.cn
  • ADDRESS:Room 1103, Block A, Wuxi National Industrial Design Park
Copy right © 2019 Wuxi Nordic Energy Technology